IEC 60038
Set of standard voltages
Set of standard voltages
International Standard IEC 60038, IEC standard voltages, defines a set of standard nominal electricity supply voltages for low voltage and high voltage AC and DC systems.
Tables
The standard primarily contains a set of tables, each of which define a set of standard nominal supply voltages that may be chosen from, as follows:
- Table 1 defines those for AC systems where voltage is to be within the range 100 to 1000.
- Table 2 defines those for DC and AC traction systems, and provides DC options from 400 to 3600, and AC options from 4750 to 27500.
- Table 3 defines those for three-phase AC systems where voltage is to be within the range 1kV to 35kV.
- Table 4 defines those for three-phase AC systems where voltage is to be within the range 35kV to 230kV.
- Table 5 defines those for three-phase AC systems where voltage is to exceed 230kV, and gives options up to 1200kV.
- Table 6 defines nominal voltages for equipment below 120 V AC, or 750 V DC.
Low voltage systems (Table 1)
Standard nominal voltages that can be used for low voltage systems in the 100-1000V range are as follows:
- For three-phase 3 or 4-wire systems at 50 Hz:
- 230/400 V
- 400/690 V
- 1000 V (3-wire)
- For three-phase 3 or 4-wire systems at 60 Hz:
- 120/208 V
- 240 V (3-wire)
- 230/400 V
- 277/480 V
- 480 V (3-wire)
- 347/600 V
- 600 V (3-wire)
- For single-phase 3-wire systems at 60 Hz (American split-phase):
- 120/240 V
Note that with the exception of the American split-phase case, where two voltages are given separated by a slash, these represent 4-wire cases; the first voltage corresponding to that between phase and neutral, and the second between phases. Single voltage values are for 3-wire cases and thus correspond to that between phases. In the case of American split-phase, the first value is that between a hot and the centre-tapped neutral, while the second is that between the pair of hots. All AC voltages are RMS. Three-phase 3-wire is without neutral, while three-phase 4-wire is with neutral.
Of historical interest, it is noted that the 230/400 V three-phase option replaced the former 220/380 V and 240/415 V systems. Similarly the 380/660 system was replaced with 400/690 V. Migration from these older voltage systems was required by amendment 2 to the 1983 edition of the standard, published in 1997. Those countries with a 220/380 V systems were required to bring their voltage within +6/-10% of 230/430 V, while those with a 240/415 V system were required to bring their voltage within +10/-6% of 230/430 V, as soon as possible, and no later than the year 2003, thus achieving all systems being within ±10% of 230/430 V by that deadline.
References
References
This article was imported from Wikipedia and is available under the Creative Commons Attribution-ShareAlike 4.0 License. Content has been adapted to SurfDoc format. Original contributors can be found on the article history page.
Ask Mako anything about IEC 60038 — get instant answers, deeper analysis, and related topics.
Research with MakoFree with your Surf account
Create a free account to save articles, ask Mako questions, and organize your research.
Sign up freeThis content may have been generated or modified by AI. CloudSurf Software LLC is not responsible for the accuracy, completeness, or reliability of AI-generated content. Always verify important information from primary sources.
Report